369-HI-R-M-0-0-0-E GE

Sale!

369-HI-R-M-0-0-0-E GE

¥2,781.00

Description

369-HI-0-M-0-0-0-E Technical Specification # Digital/Switch Input 6 Optical Isolation

Non condensing control power supply with a maximum ambient humidity of up to 95%, rated at 20VA; Maximum: 65VA Approximately: 11.5 inches high x 5.5 inches wide x 8.5 inches long fuse 3.15AH 250V Maximum altitude 2000 meters (maximum) Phase current input 1 A and 5 A Secondary

  Product Description

369-HI-0-M-0-0-E is a motor management relay manufactured by GE Multilin. The control power supply is 50-300 VDC/40-265 VAC. There is no optional RTD input on this relay. The device includes an optional metering package. There are no optional fiber optic ports. This relay provides protection and monitoring for three-phase motors and their related systems. 369 can “learn” various motor parameters and adapt to various applications. In order to improve the protection capability of the relay, users can adjust the motor surge current, cooling rate, and/or acceleration time. If you have any questions about this motor management relay or related series or manufacturer, please contact AX Control.

 

 

The set point key allows the user to browse the programmable parameter header. The actual value key allows the user to browse the measurement parameter page title. The up and down page keys can be used to scroll through the headers of actual and set values. The up and down keys can be used to scroll through subheadings. The value up and down keys allow the user to scroll through variables in setpoint programming mode. The reset button allows the user to reset the trip or lockout alarm. The Enter key can enter subgroups or store changed setpoint values. The clear key can exit a subgroup or return the changed set value to its original value. You can press the help button at any time to obtain contextual help messages.

 

SR469-P5-HI-A20-H
 

You should always ensure that the 369-HI-0-M-0-0-0-E is properly grounded. You must connect the safety grounding and filter grounding (terminals 126 and 123, respectively) to the main grounding bus in order to properly ground the device.

Common Questions about 369-HI-0-M-0-0-E 369 is designed specifically for medium voltage motors. It provides unparalleled motor protection for medium voltage AC motors by using the Motor Settings Automatic Configurator to provide simple configuration settings, advanced graphical diagnosis using Motor Health Reports, comprehensive communication using multiple communication options, and fully tracking historical reports of all device changes using safety settings changes.

 

SR469-P5-HI-A20-H(2)
 

What are the control power specifications for the 369-LO-0-MFE-0-E motor management relay?

The 369 LO-0-MFE-0-E has a low (LO) control power supply specification. The VDC range is 20-60, and the VAC control power supply range for this 369 Multilin motor management relay is 20-48. This low specification is compared to the high (HI) option, which has control power supplies of 50-300 VDC and 60-265 VAC.

What are the additional functions of the 369-LO-0-MFE-0-E Multilin General Electric digital relay?

The additional feature of 369-LO-0-MFE-0-E is an optional metering package. In addition to the individual analog outputs of the basic unit, the kit also provides three additional configurable analog outputs. The kit also provides input for power and voltage components for the device, capable of measuring various parameters such as V and kW. 369 -LO-0-MFE-0-

E also includes optional fiber optic ports, using the (F) option. This fiber optic data link is suitable for more harsh environments or for RRTD connections. The fiber sizes are 50/125, 62.5/125, 100/140, and 200 microns. The type of LED emitter is 820 nm LED with multimodality.

What is the purpose of the optional fiber optic port for 369-LO-0-MFE-0-E?

The purpose of the fiber optic port (option F) of 369-LO-0-MFE-0-E is to allow remote module RTD connections to motor management relays. Comment 369-HI-0-M-0-0-0-E

Main features

Seamless upgrade of the existing Multilin 269 motor management relay utilizing the existing Multilin 269 motor management relay withdrawable chassis to reduce system downtime, maintenance, and operational costs – no need to install kits, rework existing cuts, and rewire the chassis using automatic setting file conversion tools for easy upgrade utilizing updated, more advanced hardware and feature sets